Insulated Power Cable
Product Application and Usage Characteristics:
● This cable is suitable for power distribution and transmission lines with a rated voltage not exceeding 3.6/6kV.
● The maximum allowable long-term operating temperature of the cable is 70℃, and the maximum short-circuit temperature (within 5 seconds) is 160℃. The ambient temperature for cable installation must not be lower than 0℃.
● The allowable bending radius for single-core armored cables must not be less than 15 times the cable's outer diameter, for multi-core armored cables it is 12 times, for single-core unarmored cables it is 20 times, and for multi-core unarmored cables it is 15 times.
Standard: GB/T 12706 IEC 60502 standard, or enterprise standard.